Eismann, Ralph
E-Mail-Adresse
Geburtsdatum
Projekt
Organisationseinheiten
Berufsbeschreibung
Nachname
Vorname
Name
Suchergebnisse
CoolShift – Cooling of buildings by chiller-assisted nocturnal radiation and convection
2019-09-04, Koch, Manuel, Dott, Ralf, Eismann, Ralph, Scartezzini, Jean-Louis
A novel approach for cooling an office building is numerically evaluated. PVT collectors are used for nocturnal radiative and convective cooling. A TABS ceiling serves as thermal storage. If the free cooling power of the PVT collectors is too low, it is boosted by a chiller raising the collector temperature. While the energy efficiency improves compared to a conventional daytime chiller cooling system, the room temperature cannot always be kept in the desired band. Furthermore, the PVT collectors stay cooler than comparable PV modules during the day, increasing the electricity generation.
Pipe Network Analysis for Solar Thermal Plants
2018-09-10, Eismann, Ralph, Haeberle, Andreas
Efficiency, cost-effectiveness and operational safety of solar plants must be based on the knowledge of pressure loss as well as flow distribution and temperature distribution of branched collector arrays. Therefore, pipe network analysis is an essential step during the dimensioning process. This article presents an explicit, fast converging numerical scheme especially suited for collector fields. The effect of pipe dimensions and pipe routing on flow, temperature and pressure-distribution and collector field efficiency is demonstrated by application of a dedicated software tool, which is provided as an open source code.
An Explicit and Continuous Friction Factor Correlation for Helical Tubes with Arbitrary Roughness
2018-04-11, Eismann, Ralph, Adams, Robert
Convergence of numerical schemes for pipe network analysis requires continuous modelling of pressure losses in the transition region between laminar and turbulent regions. Several existing correlations for the friction factor of straight pipes and helical tubes are presented. Based on these correlations a new explicit correlation for helical tubes with arbitrary surface roughness is derived. The friction factor is expressed as a continuous function of the Reynolds number covering laminar, transitional, and turbulent flow regions. Potential sources of error are also discussed, including the effects of tube deformation caused by the bending process.
CoolShift. Cooling of buildings by chiller-assisted nocturnal radiation and convection
2019, Koch, Manuel, Dott, Ralf, Eismann, Ralph
A novel approach for cooling an office building is numerically evaluated. PVT collectors are used for nocturnal radiative and convective cooling. A TABS ceiling serves as thermal storage. If the free cooling power of the PVT collectors is too low, it is boosted by a chiller raising the collector temperature. While the energy efficiency improves compared to a conventional daytime chiller cooling system, the room temperature cannot always be kept in the desired band. Furthermore, the PVT collectors stay cooler than comparable PV modules during the day, increasing the electricity generation.